NLC Wireless 4-Button Switch with PIR Sensor
The NLCIWS102B1 is a line-voltage switch featuring integrated PIR occupancy and daylight sensing, with a built-in relay rated for lighting loads up to 6A. The unit consists of a 4-button interface that provides manual Dim Up, Dim Down, ON, and OFF control. Setup and commissioning require the NICOR N…
The NLCIWS102B1 is a line-voltage switch featuring integrated PIR occupancy and daylight sensing, with a built-in relay rated for lighting loads up to 6A. The unit consists of a 4-button interface that provides manual Dim Up, Dim Down, ON, and OFF control. Setup and commissioning require the NICOR NLC mobile app (iOS and Android). Note: The NLCIWS102B1 does not provide wired 0-10V dimming connections. 0-10v dimming is controlled via Bluetooth through other NLC components.
- Line-voltage Bluetooth wall switch with integrated PIR occupancy/vacancy and daylight sensing
- Built-in relay rated for loads up to 6A: 720W max at 120V and 1662W max at 277V
- 4-button interface provides manual Dim Up, Dim Down, ON, and OFF control
- 180° field of view covers up to 1200 sqft with Bluetooth mesh range up to 100Ft
- cULus Listed LED Controller, UL 8750, DLC NLC5, and UL1376 Cyber Security Certified
Color Options:
WhiteOrdering information
Downloads
Specifications
Listings & certifications
- cULus Listed
- UL 94 5VA (Flame Resistance)
- DLC NLC5 Listed
- Supports T24 Compliance
- IP20 Ingress Protection
- RoHS Compliant
Features
Construction
- IP20 Ingress Protection
- Housing Material Flame Rating: UL 94-5VA
- Color: White
Electrical
- Input voltage: 120-277VAC, 50/60 Hz
- Output voltage: 120-277VAC
- Output current: 6A max
- Output power: 720W max @120V, 1662W max @277V
- Operating temperature 0°C to 55°C (32°F to 131°F)
- Storage temperature -30°C to 85°C (-22°F to 185°F)
- Note: The NLCDWS102B1 does not provide 0-10V dimming connections
Installations
- Requires a Decora switch plate (not included)
- Ideal for retrofit applications where existing wall controls are being replaced
- Neutral conductor required
Full Listings
- cULus Listed
- UL 94 5VA (Flame Resistance)
- DLC NLC5 Listed
- Supports T24 Compliance
- IP20 Ingress Protection
- RoHS Compliant
Warranty
- 5-year limited system warranty standard
- Warranty does not cover product failure due to an overvoltage event (power surge)